Permit Number: T11CM03707
Parcel: 110120960

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T11CM03707
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/20/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Second request; sheet M-241.1 was identified in the proposal request dated May 31, 2012 as having changes but it has not been included in the review set. [Original comment: Provide sheet M-241.1 for review.]
12/20/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03707
5301 E Grant

Last review on 9/07/12, requested clearification regarding removal of main circuit breakers in panel boards, per value engineering on Proposal Request # 12, item # 1,there was no response to this request. Provide information as to what in the 2005 NEC allows removal of main breakers in all of these panels. In some situations mains are required.

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc,
12/20/2012
Ray.Majuta@tucsonaz.gov
12/21/2012 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2013 FERNE RODRIGUEZ APPROVAL SHELF Completed
01/04/2013 CPIERCE1 REJECT SHELF Completed