Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T11CM03707
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/20/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Second request; sheet M-241.1 was identified in the proposal request dated May 31, 2012 as having changes but it has not been included in the review set. [Original comment: Provide sheet M-241.1 for review.] |
| 12/20/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM03707 5301 E Grant Last review on 9/07/12, requested clearification regarding removal of main circuit breakers in panel boards, per value engineering on Proposal Request # 12, item # 1,there was no response to this request. Provide information as to what in the 2005 NEC allows removal of main breakers in all of these panels. In some situations mains are required. Ray T Majuta Elect Plan Review PDSD, C of Tuc, 12/20/2012 Ray.Majuta@tucsonaz.gov |
| 12/21/2012 | CPIERCE1 | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/04/2013 | FERNE RODRIGUEZ | APPROVAL SHELF | Completed |
| 01/04/2013 | CPIERCE1 | REJECT SHELF | Completed |