Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEETS A413 AND A274
1. Provide for and show accessible seating as required by the 2006 IBC, section 1109.11 and ICC A117.1, section 902.
SHEET A420.1
2. Provide accessible counters at the new counters added on the floor plan and referenced details D2/A420.2 and B5/A420.2.
SHEET A430.1
3. Ditto comment 2 for details A430.2/C3, E2 and F2.
END OF REVIEW
08/28/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/31/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide sheet M-241.1 for review.
09/07/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11cm03707

The Proposal Requests for # 10 and #12 need to signed by proper party.
Provide additional information on #12 for the removal of all main breakers, in other words that they are not reqiured by 2005 NEC. In some instances they are required.

Ray T Majuta
Elect Plan Ck
DSD, C of Tus
9/7/2012
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2012 CINDY AGUILAR APPROVAL SHELF Completed
12/06/2012 CINDY AGUILAR OUT TO CUSTOMER Completed
12/06/2012 FERNE RODRIGUEZ REJECT SHELF Completed