Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T11CM03707
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEETS A413 AND A274 1. Provide for and show accessible seating as required by the 2006 IBC, section 1109.11 and ICC A117.1, section 902. SHEET A420.1 2. Provide accessible counters at the new counters added on the floor plan and referenced details D2/A420.2 and B5/A420.2. SHEET A430.1 3. Ditto comment 2 for details A430.2/C3, E2 and F2. END OF REVIEW |
| 08/28/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/31/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide sheet M-241.1 for review. |
| 09/07/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11cm03707 The Proposal Requests for # 10 and #12 need to signed by proper party. Provide additional information on #12 for the removal of all main breakers, in other words that they are not reqiured by 2005 NEC. In some instances they are required. Ray T Majuta Elect Plan Ck DSD, C of Tus 9/7/2012 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/06/2012 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 12/06/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 12/06/2012 | FERNE RODRIGUEZ | REJECT SHELF | Completed |