Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03700
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/06/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM03700 6020 S Country Club 1. Sheet E-6, the 90 amp feeder installed in the existing 800 amp SES appears too small for Units CRAC 2 and CRAC 3, the total load is 67.4+56.7 amps = 124 amps. The feeder conductors also need to be upgraded. 2. Sheet E 6, size the feeders to Panels HV and HVA. 3. Sheet E 6, Panel HV feeds 75 kva transformer, Sheet E 5 Panel HVA feeds 75 kva transformer. 4. Sheet E 5, explain bottom page note stating that Panels CA and CD do not operate at the same time as CB and CC ? Fees have not been totaled on this plan. Ray T Majuta Elect Pln Ck PDSD, C of Tuc 12/07/11 Ray.majuta@tucsonaz.gov |
| 12/07/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/07/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water pressure and water pipe sizing calculations. Include the HVAC demand in the calculations. Provide the size of the existing reduced pressure back flow assembly for the building water service. Reference: Sections 604.1 and E102.2.2, IPC 2006. 2. Show that the additional water demand does not cause the existing piping to become overloaded. Reference: Sections 102.4 and 106.3.1, IPC 2006. |
| 12/08/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify how the return grilles located in room 135 are to function. Reference: Section 106.3.1, IMC 2006. 2. Coordinate the location of HP-3 and the routing of the condensate piping in the "add alternate" as shown in detail 1/M2.3 and detail 1/P1.3. Reference: Section 106.3.1, IMC 2006. 3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the mechanical units on the roof. Reference: Section 302.1, IMC 2006. 4. Clarify why no ventilation has been provided for rooms 107 and 135. Reference: Sections 401.2 and 401.3, IMC 2006. |
| 12/12/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/15/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.1; CODE REVIEW (OCCUPANT LOAD): DOES THE OCCUPANT LOAD INDICATED ON THE DRAWING INCLUDE THE NEW LOAD DUE TO THE NEW FIRST FLOOR AREA (B) AND THE REDUCED LOAD IN THE WAREHOUSE PORTION (S-1)? VERIFY. CLARIFY THE AREAS FOR OFFICE (B) AND STORAGE (S-1) AND INDICATE THOSE ON THE DRAWINGS. 2. SHEET A2.0 (FIRST FLOOR PLAN); WALL LEGEND: THE VARIOUS WALL LEGEND INDICATORS (SOLID BLACK/DASHED/POCHED) ARE NOT CLEARLY INDICATED ON THE FLOOR PLAN. REVISE. 3. SHEET A2.0; DETAILS: DETAILS 4, 5, 6, 7, 8, 10, 12, AND 13 ALL REFERENCE STRUCTURAL. REMOVE THAT REFERENCE SINCE THERE ARE NO STRUCTURAL SHEETS WITH THIS PROJECT. 4. SHEET A2.0; KEYNOTES: REMOVE THE STRUCTURAL REFERENCES FROM NOTES 2, 10, AND 20 SINCE THERE ARE NO STRUCTURAL SHEETS WITH THIS PROJECT. 5. SHEET A2.1; SECOND FLOOR PLAN: HAS THE ADD ALTERNATE AREA BEEN INCLUDED IN THE SQUARE FOOTAGE CALCULATIONS ON SHEET A1.1? HAS OCCUPANCY LOAD FOR THE ADD ALTERNATE AREA BEEN INCLUDED? INDICATE THIS ON SHEET A1.1. 6. SHEET A2.1; SECTIONS: REMOVE THE STRUCTURAL REFERENCES FROM SECTIONS 3, 4, AND 6 SINCE THERE ARE NO STRUCTURAL SHEETS WITH THIS PROJECT. 7. GENERAL: PROVIDE A FULL SIZE SITE PLAN (NEW OR LAST APPROVED) WITH THIS SET OF DRAWINGS. 8. GENERAL: THE PREVIOUS SHELL PROJECT FOR THE SECOND FLOOR ADDITION (T11CM03268) INDICATED JOIST CALCULATIONS AND REINFORCEMENT FOR MECHANICAL ADDITIONS ON THE ROOF WERE TO BE A DEFERRED SUBMITTAL. WERE THOSE SUBMITTED FOR REVIEW? 9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/20/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 12/20/2011 | SUE REEVES | REJECT SHELF | Completed |