Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM03692
Parcel: 117130410

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM

Permit Number - T11CM03692
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2011 GERRY KOZIOL WWM REVIEW Approved
12/12/2011 ANDREW CONNOR NPPO REVIEW Passed
12/14/2011 STEVE SHIELDS ZONING REVIEW Approved
12/14/2011 LEERAY HANLY BUILDING-RESIDENTIAL REVIEW Denied 1) Submitted structural plans are not sealed and state they "are not for construction" Please submit sealed construction documents. [2006 IBC SEC. 106]

2) Guard height for mezzanine to be 42" min. [IBC 1013]. The guard/handrail for stair is ok per exception to 1013.2.

3) Plumbing plans indicate TPRV and water heater pan to be drained to mop sink. There is no mop sink in this space, a good alternative would be to drain the TPRV through an air gap to a double outlet washer box. The pan may be drained to the laundry sink, but not the TPRV. [2006 UPC SEC. 608.5]

Final Status

Task End Date Reviewer's Name Type of Review Description
12/20/2011 DELMA ROBEY OUT TO CUSTOMER Completed
12/20/2011 SUE REEVES REJECT SHELF Completed