Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Permit Number - T11CM03692
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/12/2011 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 12/14/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/14/2011 | LEERAY HANLY | BUILDING-RESIDENTIAL | REVIEW | Denied | 1) Submitted structural plans are not sealed and state they "are not for construction" Please submit sealed construction documents. [2006 IBC SEC. 106] 2) Guard height for mezzanine to be 42" min. [IBC 1013]. The guard/handrail for stair is ok per exception to 1013.2. 3) Plumbing plans indicate TPRV and water heater pan to be drained to mop sink. There is no mop sink in this space, a good alternative would be to drain the TPRV through an air gap to a double outlet washer box. The pan may be drained to the laundry sink, but not the TPRV. [2006 UPC SEC. 608.5] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/20/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 12/20/2011 | SUE REEVES | REJECT SHELF | Completed |