Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM03682
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/13/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/17/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide continuous blocking for the support of the water heater. Specify how the blocking is to be connected to the metal studs and how the platform is to be connected to the blocking. |
01/17/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/17/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to verify that the use of 26 ga x 1-1/2" straps is adequate to support the proposed ductwork and meets the minimum SMACNA requirements. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/19/2012 | CINDY AGUILAR | APPROVAL SHELF | Completed |
01/19/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |