Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03682
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/06/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide the minimum plumbing facilities (e.g. a service sink) required by Table 2902.1 and Section 2902.2, IBC 2006, for mercantile and storage occupancies. See also, Section 1109.5.1, IBC 2006. |
| 12/06/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide the supporting documentation for the roof construction, as noted in footnote b of section 3 of the submitted COMcheck Envelope Compliance Certificate. [Original comment: Provide energy code compliance calculations for the building envelope and the mechanical systems. Use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.] |
| 12/06/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Need to provide mop sink as required by Table 2902.1. |
| 12/06/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM03682 3745 N I10 EB Frontage rd 1. Item # 2 last review was not addressed, the TEP Construction Book indicates that the Fault Current for the 800 amp Service can have a fault Current of 55,660 AIC, the sevice must bring this value down to a level the electrical equipment can safely handle. NEC 2005 Section 110.9 and 110.22 require the Fault Current meet adaquate levels. Ray Majuta Elect Pln CK PDSD, C of Tuc, 12/6/11 Ray.majuta@tucsonaz.gov |
| 12/09/2011 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
| 12/09/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |