Permit Number: T11CM03682
Parcel: 10309068D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03682
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Need to provide mop sink as required by Table 2902.1.
12/06/2011 ROBERT SHERRY WATER REVIEW Approved
12/06/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide the minimum plumbing facilities (e.g. a service sink) required by Table 2902.1 and Section 2902.2, IBC 2006, for mercantile and storage occupancies. See also, Section 1109.5.1, IBC 2006.
12/06/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03682
3745 N I10 EB Frontage rd

1. Item # 2 last review was not addressed, the TEP Construction Book indicates that the Fault Current for the 800 amp Service can have a fault Current of 55,660 AIC, the sevice must bring this value down to a level the electrical equipment can safely handle. NEC 2005 Section 110.9 and 110.22 require the Fault Current meet adaquate levels.


Ray Majuta
Elect Pln CK
PDSD, C of Tuc,
12/6/11
Ray.majuta@tucsonaz.gov
12/06/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide the supporting documentation for the roof construction, as noted in footnote b of section 3 of the submitted COMcheck Envelope Compliance Certificate. [Original comment: Provide energy code compliance calculations for the building envelope and the mechanical systems. Use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.]
12/09/2011 CPIERCE1 ENGINEERING REVIEW Needs Review
12/09/2011 CPIERCE1 WWM REVIEW Needs Review