Permit Number: T11CM03665
Parcel: 122050550

Address:
4349 E EDISON ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM03665
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2011 GERRY KOZIOL WWM REVIEW Approved
12/19/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 12-21-11
Activity: T11CM03665
Address: 4349 E Edison St
Applicant: Jim Kubiar

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide a minimum 2'8" panel on either side of the garage for alternate braced wall designs per R602.10.6 or specify another approved alternative.
2. Specify foundation hold-downs for alternate brace wall panels that have minimum uplift capacity of 1800 lbs, R602.10.6 (HPAHD42 are insufficient).
3. Show the location of attic access min. 22"x30", R807.

OUTDOOR LIGHTING CODE:
4. Bulbs specified for flood lighting (unshielded) are rated at 1050 lumens each. Two fixtures with two bulbs each would be 4200 lumens which would exceed the lot allowance. Clarify

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2012 CPIERCE1 OUT TO CUSTOMER Completed
01/04/2012 SUE REEVES REJECT SHELF Completed