Permit Number: T11CM03661
Parcel: 11717023E

Address:
88 E BROADWAY BL

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T11CM03661
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2011 PAUL MACHADO ENGINEERING REVIEW Approved
12/09/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/09/2011 TERRY STEVENS ZONING REVIEW Approved
12/09/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11C03661
88 E Broadway
61.44 KW Photovoltaic System

Electrical Plans for the following denied:
1. Provide specification sheets for the modules, inverter,
and combiner box.
2. Show the grouping of arrays and number them.
3. Provide locations on plan for combiner boxes, inverter, and disconnects.
4. Provide a three line diagram as well as the one line.
5. All electrical sheets to be sealed by EE.
6. Provide the fault current value at MSB and how let thur value sufficient for equipment downstream, per NEC 110.9.
7. Provide the wiring methods to be used to connect module panels along with sizes and conduits if used.
8. Where on sheet E401 is MSB located?
9. Indicate on plans all required warning signs in be installed on equipment as required per NEC 690.
10.Do not add to plan in pen or pencil after change or to
include information.

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
12/9/2011
Ray.majuta@tucsonaz.gov
12/09/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied ELECTRICAL SPECIFICATIONS ARE INCOMPLETE

1) PROVIDE COMPLETE SPECIFICATIONS AND INFORMATION NECESSARY TO EVALUATE COMPLINACE WITH THE 2008 NEC, PARTICULARLY NEC 690.

a) Derating factors used for conductors with conductor sizes and types
b) Terminations at utility interaction point
c) Ground termination points
d) Required signage
c)
12/09/2011 LHANLY1 ADA REVIEW Approved
12/12/2011 LHANLY1 FIRE REVIEW Denied