| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2011 | ANY | BUILDING-COMMERCIAL | REVIEW | Active | |
| 11/30/2011 | ANY | ZONING | REVIEW | Active | |
| 11/30/2011 | ANY | ELECTRICAL-COMMERCIAL | REVIEW | Active | |
| 12/01/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | This comments apply to the job as a whole and will be repeated for all activity numbers. 1) Fire Department approved lock boxes will be required at sliding gates. 2) Fire sprinklers will need to be installed in building A. Reference 2006 IFC, section 903.2.7. 3) An alarm system will be required in all residential buildings except those containing fire sprinklers. Reference 2006 IFC, section 907.3.6. 4) Please provide clarification regarding separation between Building A and Leasing building. Are they connected by a roof structure? Do they require fire wall separation? |
| 12/05/2011 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 12/05/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/05/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 12/06/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the plumbing code to be used for this activity. The plumbing General Notes on sheet P3.1 refer to the 2006 UPC but the Code analysis on sheet T1.1 refers to the 2006 IPC. This review has been made using the 2006 UPC. 2. Provide dimensions for the scupper overflow shown in detail 2/A7.1. Reference: Sections 103.2.3 and 1101.11.2.1, UPC 2006. |