Permit Number: T11CM03645
Parcel: 11205030B

Review Status: Active

Review Details: COMMERCIAL - NEW

Permit Number - T11CM03645
Review Name: COMMERCIAL - NEW
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2011 ANY BUILDING-COMMERCIAL REVIEW Active
11/30/2011 ANY ZONING REVIEW Active
11/30/2011 ANY ELECTRICAL-COMMERCIAL REVIEW Active
12/01/2011 MARTIN BROWN FIRE REVIEW Denied This comments apply to the job as a whole and will be repeated for all activity numbers.
1) Fire Department approved lock boxes will be required at
sliding gates.
2) Fire sprinklers will need to be installed in building A. Reference 2006 IFC, section 903.2.7.
3) An alarm system will be required in all residential buildings
except those containing fire sprinklers. Reference 2006
IFC, section 907.3.6.
4) Please provide clarification regarding separation between
Building A and Leasing building. Are they connected by
a roof structure? Do they require fire wall separation?
12/05/2011 ROBERT SHERRY WATER REVIEW Passed
12/05/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/05/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
12/06/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the plumbing code to be used for this activity. The plumbing General Notes on sheet P3.1 refer to the 2006 UPC but the Code analysis on sheet T1.1 refers to the 2006 IPC. This review has been made using the 2006 UPC.
2. Provide dimensions for the scupper overflow shown in detail 2/A7.1. Reference: Sections 103.2.3 and 1101.11.2.1, UPC 2006.