Permit Number: T11CM03632
Parcel: 10510010D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03632
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2011 RICK HOLLANDER ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03632
333 E Wetmore # 225

1. New Panel RP2W2 shows all circuitry on plan, all other relocated receptacles show per new work note 6 on sheet E1.1 to extend and reconnect to existing circuit. In minor situations that would suffice, however on this plan the majority of receptacles have been relocated, please include circuit number and panel they feed from and provide a panel schedule.
2. Provide a panel schedule for LP2W, since several circuits are being added to it.

Ray Majuta
Elect Pln Ck
PDSD, C o T
12/03/11
Ray.majuta@tucsonaz.gov
12/07/2011 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2012 CPIERCE1 OUT TO CUSTOMER Completed
01/06/2012 SUE REEVES REJECT SHELF Completed