Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM03632
Parcel: 10510010D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03632
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2011 STEVE SHIELDS ZONING REVIEW Approved
11/28/2011 LAITH ALSHAMI ENGINEERING REVIEW Approved
11/29/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/29/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/29/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/29/2011 ROBERT SHERRY WATER REVIEW Approved
11/29/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Verify that the reduced pressure backflow preventer and the double check valve located adjacent to P-1 conform to the access and clearance requirements of Sections 304.0 and 603.3.4, UPC 2006.
2. Show that the atmospheric vacuum breaker located in room 128 conforms to the access and clearance requirements of Sections 304.0 and 603.3.4, UPC 2006.
3. Indirect waste receptors shall not be installed in a closet or cupboard. Reference: Section 804.1, UPC 2006.
4. Verify that the water heater, WH-1, has controls capable of allowing a setpoint of 90 degrees Fahrenheit. Reference: Section 504.3, IECC 2006.
11/29/2011 DAVE MANN FIRE REVIEW Approved
11/29/2011 RONALD BROWN ADA REVIEW Passed
11/29/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/30/2011 CPIERCE1 WWM REVIEW Needs Review