Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03590
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/22/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/22/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 11/22/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/22/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/22/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/02/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the manufacturer's listing information for the Type I hood. 2. Revise the outside air calculations, correcting the arithmetic and performing the common ventilation calculation per Section 403.3.1, IMC 2006. 3. Verify the separation of the exhaust outlet from EF-1 from AC-2. 4. Verify the separation of the exhaust outlets from EF-4 and EF-5 from EC-1. 5. Verify the separation of the exhaust outlet from EF-2 from AC-1. |
| 12/02/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/02/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/02/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | OK to submit |
| 12/06/2011 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 12/06/2011 | CPIERCE1 | ZONING | REVIEW | Needs Review |