Permit Number: T11CM03590
Parcel: 107051030

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03590
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/22/2011 PAUL MACHADO ENGINEERING REVIEW Approved
11/22/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/22/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/22/2011 ERIC NEWCOMB ADA REVIEW Passed
12/02/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the manufacturer's listing information for the Type I hood.
2. Revise the outside air calculations, correcting the arithmetic and performing the common ventilation calculation per Section 403.3.1, IMC 2006.
3. Verify the separation of the exhaust outlet from EF-1 from AC-2.
4. Verify the separation of the exhaust outlets from EF-4 and EF-5 from EC-1.
5. Verify the separation of the exhaust outlet from EF-2 from AC-1.
12/02/2011 DAVE MANN FIRE REVIEW Approved
12/02/2011 ROBERT SHERRY WATER REVIEW Approved
12/02/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review OK to submit
12/06/2011 CPIERCE1 WWM REVIEW Needs Review
12/06/2011 CPIERCE1 ZONING REVIEW Needs Review