Permit Number: T11CM03586
Parcel: 12604266B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03586
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
11/28/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/28/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
11/28/2011 ROBERT SHERRY WATER REVIEW Approved
11/28/2011 FRODRIG2 BUILDING-COMMERCIAL REVIEW Approved
11/28/2011 FRODRIG2 ENGINEERING REVIEW Approved
11/28/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a direct connection to the grease waste system for the wash and rinse sections of the 3-compartment sink.
2. Provide a means to limit the water temperature for the new lavatory to no more than 110 degrees Fahrenheit.
3. Specify the materials of construction for the plubing vents.
11/28/2011 MARTIN BROWN FIRE REVIEW Approved
11/28/2011 FRODRIG2 ADA REVIEW Passed
11/28/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/29/2011 GERRY KOZIOL WWM REVIEW Approved