Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03582
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2012 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 08/15/2012 | CPIERCE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/15/2012 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/15/2012 | CPIERCE1 | WATER | REVIEW | Needs Review | |
| 08/15/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 08/15/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 08/15/2012 | CPIERCE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 08/15/2012 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
| 12/07/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations 2. Toilets do not comply with ANSI 117.1, Section 604.3, toilet clearances. 3. Shower does not comply with ANSI 117.1, Section 608.2.3. 4. Please show all assessible code requirements on the floor plan and elevations: i.e. dimensions, clearances, fixtures and accessories. 5. Call out 1 hour rated wall next to property line. END OF REVIEW |
| 12/07/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 12/07/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |