Permit Number: T11CM03564
Parcel: 140418490

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03564
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; show the new design on the drawings. Provide information to show how the proposed water heater support is to be connected to the building structure. Reference: Section 314.5, UPC 2006.
2. The revision of the building drain has resulted in the lack of a properly-sized cleanout for the new 4" pipe. Reference: Section 707.11, UPC 2006.
12/08/2011 GERRY KOZIOL WWM REVIEW Approved
12/14/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/19/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved