Permit Number: T11CM03564
Parcel: 140418490

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03564
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEETS IA1.0 AND IA1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE SECTIONS, DIMENSIONS, ELEVATIONS, AND ROOM NUMBERS.
2. SHEET IA2.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE DIMENSIONS AND ELEVATIONS.
3. SHEET IA3.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE WALL FRAMING DETAIL 1.
4. SHEET IA3.0; DETAILS 1 A/B: ENLARGE DETAILS TO INDICATE BRACING AT THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE. INCLUDE BRACING SIZE, MEMBER SIZES TO THE EXISTING STRUCTURE ABOVE, AND CONNECTION SIZES AND QUANTITIES.
5. SHEET IA4.0; RESTROOM ELEVATIONS: LOCATE THE VERTICAL GRAB BAR FROM THE BACK WALL.
6. GENERAL: PROVIDE ENLARGED RESTROOM PLANS, INDICATING CRITICAL DIMENSIONS FOR ACCESSIBILITY.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/17/2011 ERIC NEWCOMB ADA REVIEW Passed
11/17/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
11/18/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show how the proposed water heater support is to be connected to the building structure. Reference: Section 314.5, UPC 2006.
2. Resize the drainage piping to conform to Table 7-5, UPC 2003, with no more than 8 fixture-units on a 2" horizontal waste line. Reference: Section 703.2, UPC 2006
11/18/2011 ROBERT SHERRY WATER REVIEW Approved
11/18/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
11/18/2011 JASON GREEN ENGINEERING REVIEW Approved
11/18/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/18/2011 MARTIN BROWN FIRE REVIEW Approved
12/01/2011 CAGUILA1 WWM REVIEW Needs Review