Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM03540
Parcel: 136261300

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03540
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide material standards for all plumbing fixtures being provided by others. Reference: Section 303.4, IPC 2006.
2. Provide the specifications and listing information for the proposed water heater. Reference: Sections 106.3.1, 303.2, and 501.5, IPC 2006.
3. Show that there is adequate space within the cabinetry for maintenance and replacement of the water heater and expansion tank. Reference: Sections 501.4 and 502.1, IPC 2006.
4. Provide a direct connection for the 2-compartment sink. Reference: Sections 301.3 and 802.1, IPC 2006.
5. Indirect waste receptors shall be not be installed in bathrooms, toilet rooms, or in inaccessible or unventilated spaces (e.g. cupboards, storerooms, or closets). Reference: Section 802.3, IPC 2006.
11/21/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied The riser diagram was requested last review,still only showing the service connected to a possible gutter wing.

Ray T Majuta
Elect Pln Ck
PDSD, C of Tuc
11/22/2011
11/30/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied The resubmittal review comments were provided by Ron Brown for the original plan review comments of Eric Newcomb.

1. SHEETS A1, A2, A3, AND A4 (BUSINESS AND TRAINING): THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THESE SHEETS.
Resubmittal Comments:
a. The reference to 3/32" minimum height for lettering means the actual physical size, not the CAD nomenclature. Most all sheets here have lettering smaller than 3/32" including mechanical and electricaL. Please revise all sheets to the required COT standard and resubmit.

2. ok

3. ok

4. SHEETS A1 (BUSINESS AND TRAINING): PROVIDE ENLARGED PLANS OF THE RESTROOMS (SPECIFIC TO THIS JOB, NOT 'TYPICAL'), AND ENLARGED RESTROOM DETAILS, INDICATING ALL HEIGHTS, LENGTHS, AND LOCATIONS OF ALL GRAB BARS, PAPER DISPENSER, AND WATER CLOSET PER ICC/ANSI A117.1-2003, CHAPTER 6.
Resubmittal Comments:
a. All toilets are non compliant with the 2006 IBC, Section 1210.2 Wall Material. Please correct all toilet elevations for compliance with this section and resubmit.

5. ok

6. ok

7. ok

8. SHEETS M1 (BUSINESS AND TRAINING); EXHAUST FAN DETAIL: PROVIDE ENLARGED DETAILS OF HOW THE EXHAUSE FAN SUPPORT RODS ARE CONNECTED AT THE ROOF.
Resubmittal Comment:
a. Detail is too vague. Please provide complete structural calculations and complete descriptive details.

9. GENERAL: THE IBC TABLE 2902.1 REQUIRES ONE HIGH/LOW DRINKING FOUNTAIN, OR A SINGLE POINT-OF-USE WATER DISPENSER. INDICATE ON THE PLAN.
Resubmittal Comments:
a. Bottled water is not "A Point of Use Water Dispenser". Please contact Mr. Bob Sherry (837-4914), our plumbing reviewer, and he will provide you a product reference. Please revise and resubmit.

10. ok

11. ok

12. For the 2nd resubmittal, please provide the reviewer's comments along with your written response.

END OF RESUBMITTAL COMMENTS