Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03532
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. For the purpose of determining additional plan review fees, please provide a summary letter for deferred submittals to the building official, R. Ron Boose. 2. Please provide additional special inspection certifications for bolts in concrete, epoxy bolts, expansion anchors and foundation excavation. 3. Please provide structural calculations for the following: a. Electrical light pole foundations b. Suspended fan coil units END OF REVIEW |
| 11/18/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/21/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Architectural detail 6/A4 and section 1/A6.1 indicate the presence of a roof drain and overflow drain; where does this occur? Reference: Section 106.3.1, IPC 2006. |
| 11/21/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | . |
| 11/21/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the energy code analysis for the building envelope, coordinating building area and the building components used in the analysis with those shown on the drawing. Reference: Section 502, IECC 2006, as amended by the City of Tucson. 2. Show the size and termination of the condensate drain from FC-2. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson. |
| 11/22/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | need demo plans showiing plumbing fixtures removed for credit & need 5th floor WW credit evaluation - 740-6602 |
| 12/02/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 12/07/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/22/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 12/22/2011 | SUE REEVES | REJECT SHELF | Completed |