Permit Number: T11CM03525
Parcel: 13323359A

Address:
199 N PANTANO RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T11CM03525
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. The methodology of presenting project changes for review is somewhat confusing:
a. Some sheets are scheduled to have changes in the title block menu but no changes are identified on the sheet. The nationally accepted standard for identifying changes is to cloud the change and provide a numbered delta with the date of the change.
b. The following sheets that show scheduled changes which are not identified are: T1, A1, A1.1, A5.1, A5.2, A5.3 PP1.1, EL1.2 and EL 1.3.
c. Please identify the architectural and structural changes only with a cloud and a dated and numbered delta and resubmit.
d. As per previous comments, finish changes do not required a drawing revision change approval. Please eliminate all finish changes and resubmit.
2. Sheets that schedule changes and are identified with a cloud but have no numbered delta with a date for change are: G1, A3.1, A3.2, DP1, RC1, RC1.1, MW1, MW2, MW3, PP1, PP1,2, WS1, SS1, SS1.1, SS1.2, FP1, FP1.1, WF1, WF1.1, EL1, EL1.1, F1, F2 and S1.
a. Please provide all architectural and structural changes with dated and numbered delta.
b. Please remove all finish changes and resubmit.
END OF REVIEW
04/10/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/25/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed