Permit Number: T11CM03525
Parcel: 13323359A

Address:
199 N PANTANO RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03525
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Reference previous comment number 2:
The correction on sheets PP1 and PP1.1 are now correctly referenced to structural wall details provided on sheet S1.1 however details 1/S1.1 through 3/S1.1 and 4/S1.1 through 9/S1.1 do not comply with Section 1601.13 being attached to the ceiling grid. Diagonal bracing at 4'-0" o.c. to the structure above and directly attached to the metal partition studs is an acceptable method of compliance.
END OF REVIEW
01/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved