Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/04/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Reference previous comment number 2: The correction on sheets PP1 and PP1.1 are now correctly referenced to structural wall details provided on sheet S1.1 however details 1/S1.1 through 3/S1.1 and 4/S1.1 through 9/S1.1 do not comply with Section 1601.13 being attached to the ceiling grid. Diagonal bracing at 4'-0" o.c. to the structure above and directly attached to the metal partition studs is an acceptable method of compliance. END OF REVIEW |
01/11/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |