Permit Number: T11CM03525
Parcel: 13323359A

Address:
199 N PANTANO RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03525
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. The COT minimum font size is 3/32" upper and lower case. Several of your sheets, including other disciplines, do not meet this minimum requirement. Please revise all sheets to meet this minimal standard and resubmit.
SHEETS PP1 AND PP1.1
2. Please indicate how all new partitions meet the requirements of the 2006 IBC, Section 1601.13, horizontal load resistance.
SHEET S1
3. Please provide structural calculations.
4. Ditto Comment 3.
END OF REVIEW
11/15/2011 WMOTTO1 FIRE REVIEW Approved
11/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/18/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
11/18/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/18/2011 ROBERT SHERRY WATER REVIEW Approved
12/02/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03525
199 N Pantano
Kolh's TI Remodel

1. Sheet E1 on lighting indicates fixtures being added to existing circuitry, need to identy circuit and verify new load can be handled by circuit, this is accomplished by providing a panel schedule and indicating new load total.
2. E2 power sheet same as item #1 above , added power to existing circuitry to be identified and panel changed to reflect new loads.

Ray Majuta
Elect Pln Ck
PDSD, C of T,
12/4/11
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2011 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
12/23/2011 SUE REEVES REJECT SHELF Completed