Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03516
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/14/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
11/14/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust shall operate whenever air is being supplied to the restroom). Reference: Section 403.2.1 (4), IMC 2006. Comment corrected 11/14/11 |
11/14/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/14/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/14/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/14/2011 | SREEVES1 | WWM | REVIEW | Needs Review | |
11/14/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | Provide specifications for the proposed mop sink along with the size of the drain pipe. Comment corrected 11/14/11 |
11/14/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
11/14/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
11/14/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
11/14/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/14/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |