Permit Number: T11CM03492
Parcel: 125091980

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM03492
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2011 DAVE MANN FIRE REVIEW Approved
11/16/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03492
225 N Country Club
Photovoltaic System


1. Provide specification sheets for Photovoltaic equipment, modules,inverters and combiner boxes.
2. Sheet PV 2. note 20 indicates a line side interconnection to comply with 690.64(A), the actual tie in will be on the supply side. The owner of the existing primary switch is called out to be the occupant.Thus being the case, the interconnection will be on the supply side and would need to comply with 690.64-(B).1 and 2. Provide required information and compliance.
3. Provide a cut sheet on type of connector to be used on double bolt connection to 1200 amp line.
4. Under labeling notes include reference to 690.54 and 56.(B).


Ray T Majuta
Elect Plan Review
PDSD, C of T
11/15/11
Ray.majuta@tucsonaz.gov
11/21/2011 PAUL MACHADO ENGINEERING REVIEW Approved
11/21/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
11/21/2011 GBONILL1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/21/2011 GERARDO BONILLA OUT TO CUSTOMER Completed