Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T11CM03492
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/16/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM03492 225 N Country Club Photovoltaic System 1. Provide specification sheets for Photovoltaic equipment, modules,inverters and combiner boxes. 2. Sheet PV 2. note 20 indicates a line side interconnection to comply with 690.64(A), the actual tie in will be on the supply side. The owner of the existing primary switch is called out to be the occupant.Thus being the case, the interconnection will be on the supply side and would need to comply with 690.64-(B).1 and 2. Provide required information and compliance. 3. Provide a cut sheet on type of connector to be used on double bolt connection to 1200 amp line. 4. Under labeling notes include reference to 690.54 and 56.(B). Ray T Majuta Elect Plan Review PDSD, C of T 11/15/11 Ray.majuta@tucsonaz.gov |
| 11/21/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 11/21/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/21/2011 | GBONILL1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/21/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |