Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural calculations for all new roof top mounted HVAC units and suspended fan coil units, including structural details.
END OF REVIEW
11/23/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/23/2011 ROBERT SHERRY WATER REVIEW Approved
11/23/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The civil site drawing shows that the rim elevation of the next upstream manhole is less than 12" below the first floor elevation. Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson. Fixtures located on floor levels above the first floor elevation of the building shall not drain through the backwater valve. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson.
11/28/2011 GERRY KOZIOL WWM REVIEW Approved