Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03491
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/23/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide structural calculations for all new roof top mounted HVAC units and suspended fan coil units, including structural details. END OF REVIEW |
11/23/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
11/23/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/23/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The civil site drawing shows that the rim elevation of the next upstream manhole is less than 12" below the first floor elevation. Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson. Fixtures located on floor levels above the first floor elevation of the building shall not drain through the backwater valve. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson. |
11/28/2011 | GERRY KOZIOL | WWM | REVIEW | Approved |