Review Details: COMMERCIAL - TI

Permit Number - T11CM03491
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2011 STEVE SHIELDS ZONING REVIEW Approved
11/10/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify how ventilation will be supplied to the future tenant from FC-1 which serves both tenant areas but is controlled from the the present tenant's area. Reference: Section 403, IMC 2006.
11/10/2011 RONALD BROWN ADA REVIEW Passed
11/10/2011 ROBERT SHERRY WATER REVIEW Denied Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 106.3.1, IPC 2006.
11/10/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Occupant load for Business as per table 1004.1 is 1/100 sf which calculates to a maximum occupant load of 97. To attain an occupant load as indicated on your code data summary of 200, an appeal to the building offical must be obtained.
2. At detail 3/A3.0, please provide vertical grab bar.
3. At detail 1/A3.0:
a. Show accessible clearances as required by ICC/ANSI 117.1, 2003 Edition, Chapter 6.
b. Show drinking fountains and required clearances as per Section 602.
SHEET A/1.0
4. Verify and show required clearances at drinking fountain.
SHEET A/3.0
5. Detait A is not as designed on sheet A1.0. Reconcile and resubmit. Generic details are not acceptable.
6. Please provide last approved site Plan.
7. Please provide structural calculations for all new roof top mounted HVAC units and suspended fan coil units, including structural details.
END OF REVIEW
11/10/2011 LAITH ALSHAMI ENGINEERING REVIEW Approved
11/10/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water supply and sanitary waste systems to become overloaded. Reference: Section 102.4, IPC 2006.
11/10/2011 MARTIN BROWN FIRE REVIEW Approved
11/10/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
11/14/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/23/2011 GBONILL1 WWM REVIEW Needs Review