Permit Number: T11CM03458
Parcel: 130130850

Address:
2421 S 34TH PL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03458
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03458
2421 S 34th Pl
Photovoltaic System

1. The plan states that it is to be installed under the 2005 NEC. 690.64.B-- allows only 100% of the rated bus to be used (225 amps) , per the supplying power overcurrent devices being 40 amps and 200 amps-- these equal 240 when the bus is rated at onlu 225 amps.
2. The plan can be used according to the 2008 NEC, however different requirements apply, In order to use according to the 2008 NEC, indicate on the plan that the correct code is to be used and the installation will comply with that year.

Ray T Majuta
Elect Pln Review,
PDSD, C of Tuc,
11/28/11