Permit Number: T11CM03457
Parcel: 132166440

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03457
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2011 STEVE SHIELDS ZONING REVIEW Approv-Cond
11/04/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/04/2011 ROBERT SHERRY WATER REVIEW Approved
11/04/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide two toilet rooms as required by 2006 IBC, Section 2902.2.2.
2. Please provide water dispenser as per 2006 IBC, Section 1109.5
3. Please provide service sink as per Table 2902.1.
4. Please redraw toilet elevations to actual design conditions.
END OF REVIEW
11/04/2011 DROBEY1 WWM REVIEW Needs Review
11/04/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Check the size of the trap for sink P-3 (Secvice sink requires a 2" trap).
2. Provide a drinking fountain or water dispenser.
11/04/2011 PAUL MACHADO ENGINEERING REVIEW Approved
11/04/2011 DROBEY1 FIRE REVIEW Needs Review
11/04/2011 RONALD BROWN ADA REVIEW Passed
11/04/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2011 DELMA ROBEY OUT TO CUSTOMER Completed