Permit Number: T11CM03455
Parcel: 133047570

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03455
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 1-11-12
Activity: T11CM03455 2nd review
Address: 1485 N Hidden Glen Rd
Applicant: Jim Sullivan

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Specify beams on the ramada sized for the proposed span.

PLUMBING PLAN:
2. The Uniform Plumbing Code and the International Plumbing Code are not interchangeable. Only one code may be specified for a plumbing design. Notes provided indicate plumbing to comply with the IRC and the fixture unit schedule has UPC values. Clarify.
3. Provide an accurate plumbing fixture unit schedule.
4. Provide a water supply line from the water meter sized for the proposed demand.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review
01/13/2012 CPIERCE1 WWM REVIEW Needs Review