Permit Number: T11CM03454
Parcel: 11618348C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03454
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2011 MARTIN BROWN FIRE REVIEW Approved
12/09/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct the waste and vent riser diagram; coordinate with the plumbing plan.
2. The prep sink, the condensate from the ice maker, and the ice melt from the ice maker shall be indirectly wasted.
3. Provide a vent and cleanout downstream of the grease
interceptor.
4. Finish labeling the pipe sizes on the gas riser diagram; coordinate with the plumbing plan.
12/09/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the proposed ventilation rate meets or exceeds the requirements of Section 403.3, IMC 2006.
2. Provide more complete descriptions of the proposed supply fan and hood exhaust fan (e.g. manufacturer and model number).
12/14/2011 GBONILL1 WWM REVIEW Needs Review
12/14/2011 GBONILL1 ZONING REVIEW Needs Review