Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03454
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/09/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/09/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Correct the waste and vent riser diagram; coordinate with the plumbing plan. 2. The prep sink, the condensate from the ice maker, and the ice melt from the ice maker shall be indirectly wasted. 3. Provide a vent and cleanout downstream of the grease interceptor. 4. Finish labeling the pipe sizes on the gas riser diagram; coordinate with the plumbing plan. |
| 12/09/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the proposed ventilation rate meets or exceeds the requirements of Section 403.3, IMC 2006. 2. Provide more complete descriptions of the proposed supply fan and hood exhaust fan (e.g. manufacturer and model number). |
| 12/14/2011 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 12/14/2011 | GBONILL1 | ZONING | REVIEW | Needs Review |