Permit Number: T11CM03454
Parcel: 11618348C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03454
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/04/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a mechanical design for the new hood system.
11/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Electrical -- electrical sheet shows a 400 amp main disconnect feeding a 200 amp panel, with one existing 200 amp panel being removed,please clarify.

Ray T Majuta
PDSD CoF Tucson
11/4/11
11/04/2011 ROBERT SHERRY WATER REVIEW Approved
11/04/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a waste and vent riser diagram.
2. Contact Doug Kirkland (443-6202) to determine which fixtures must be connected to the grease intercepter.
3. The prep sink, the condensate from the ice maker, and the ice melt from the ice maker shall be indirectly wasted.
4. Show the revisions to the gas piping on the plumbing drawing. Include all of the gas loads and the developed pipe length from the gas meter to each gas load.
11/04/2011 PAUL MACHADO ENGINEERING REVIEW Approved
11/04/2011 RONALD BROWN ADA REVIEW Passed
12/02/2011 DROBEY1 WWM REVIEW Needs Review
12/02/2011 DROBEY1 ZONING REVIEW Needs Review
12/02/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/02/2011 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2011 DELMA ROBEY OUT TO CUSTOMER Completed