Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03444
4798 S Julian

1. The Paint Booth is not Listed or Approved by any Nationally Recognized Testing Laboratory -- approved by OSHA, only individual component listing shown. The area around and in the Paint booth is classified as Hardous Locations per 2005 NEC 516. All wiring not covered by a listing must be included on the plan including any control panel, interlocking, wiring of lighting,any wiring in Hazardous Locations.
2. The Sand Blast Booth does not show any wiring other than connection to the starter and switch for lighting and receptacle power ?

Ray Majuta
Elect Pln Ck
PDSD, C o T
12/3/11