11/18/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 11-18-11
Activity: T11CM03435
Address: 3145 N Willow Creek Dr
Applicant: MPE

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Specify lateral reinforcement for roof framing by one of the following methods:
o Provide vertical support at outside end of 6x12 ridge beam
o Specify and detail moment connections for angled roof beam connections to columns
o Provide horizontal tie at top of columns to resist outward pressure

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review