Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 7: DETAIL C/A-12 INDICATES A DOUBLE ANGLE OVER THE NEW DOOR OPENING, WHILE DETAIL 1/A-8 INDICATES A WIDE FLANGE. WHAT IS THE REFERENCE TO SHEET A-1? PROVIDE STRUCTURAL CALCULATIONS FOR THE DOOR LINTELS AND COORDINATE THE DETAILS.
2. PREVIOUS COMMENT 10: DETAIL 1/A-11 INDICATES A 3X3X 1/2 STEEL COLUMN. PROVIDE THE STRUCTURAL CALCULATIONS AND DETAILS FOR THE COLUMN, THE COLUMN CONNECTION TO THE WALL, ETC.
3. PREVIOUS COMMENT 12: THE NOTE INDICATES A BOND BEAM, BUT THE SECTION INDICATES A STEEL BEAM. CLARIFY. PROVIDE STRUCTURAL CALCULATIONS FOR DOOR LINTELS.
4. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS.
11/22/2011 ERIC NEWCOMB ADA REVIEW Passed
11/22/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/23/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/23/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/23/2011 ROBERT SHERRY WATER REVIEW Approved
11/23/2011 LOREN MAKUS ENGINEERING REVIEW Approved
11/28/2011 GERRY KOZIOL WWM REVIEW Denied need to show location of connection
need WW/IWC review of grease interrceptor - Tom Tomchak 5025 W Ina Rd - 443-6200
clarify size of FD's (2",3" or 4")
need credit evaluation 5th floor 740-6606
need to show location of grease interceptor
11/29/2011 DAVE MANN FIRE REVIEW Approved
11/30/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PREVIOUS COMMENT #2) Provide cut sheets for outdoor lighting and any required lumen calculations to show compliance with the City of Tucson / Pima County Outdoor Lighting Code

This comment has not been fully addressed. The only cut-sheet provided is for a wall-pack flood light, the goose-neck F2A fixtures have not been addressed. Please provide information for the F2A fixtures, and show how all additional exterior lighting remains within complince to the City of Tucson Outdoor Lighting Code.

If you have questions they may be addressed to LeeRay.Hanly@tucsonaz.gov
11/30/2011 STEVE SHIELDS ZONING REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2011 DELMA ROBEY REJECT SHELF Completed