Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) Provide IECC lighting compliance certificate

2) Provide cut sheets for outdoor lighting and any required lumen calculations to show compliance with the City of Tucson / Pima County Outdoor Lighting Code

3) Provide available ground fault information and calculations to justify AIC rating of new panels.

4) Provide corrected interlock diagram (or remarks) for EF-1 and EF-2 to show compliance with IMC 403.2.1. (exhaust must run when air is introduced into restrooms)

5) All single phase 15A & 20A plug receptacles in kitchen and prep areas to be GFCI protected. NEC 210.8(B)
(Exception may be made for POS system with IG)