Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03423
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) Provide IECC lighting compliance certificate 2) Provide cut sheets for outdoor lighting and any required lumen calculations to show compliance with the City of Tucson / Pima County Outdoor Lighting Code 3) Provide available ground fault information and calculations to justify AIC rating of new panels. 4) Provide corrected interlock diagram (or remarks) for EF-1 and EF-2 to show compliance with IMC 403.2.1. (exhaust must run when air is introduced into restrooms) 5) All single phase 15A & 20A plug receptacles in kitchen and prep areas to be GFCI protected. NEC 210.8(B) (Exception may be made for POS system with IG) |
| 11/22/2011 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 11/22/2011 | FRODRIG2 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/22/2011 | FRODRIG2 | FIRE | REVIEW | Needs Review | |
| 11/22/2011 | FRODRIG2 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/22/2011 | FRODRIG2 | WATER | REVIEW | Needs Review | |
| 11/22/2011 | FRODRIG2 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/22/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/22/2011 | FRODRIG2 | ADA | REVIEW | Needs Review |