Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03423
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-1 (DIMENSION PLAN); SHEET A-8 (PARTITION TYPES): VERIFY THE WALLS FOR THE EXIT CORRIDOR TO THE WEST EXIT MEET THE 2006 IBC TABLE 1017.1 FOR FIRE RESISTANCE AND DOORS MEET TABLE 715.4. 2. SHEET A-1 (DIMENSION PLAN); SHEET A-8 (PARTITION TYPES): THE PLAN INDICATES A WALL TYPE P1A, BUT THE PARTITION TYPES DO NOT INCLUDE THAT REFERENCE. VERIFY. 3. SHEET A-1.1; FLOOR PLAN: PER THE IBC SECTION 1005.2, DOORS OPENING INTO THE PATH OF EGRESS TRAVEL HAVE LIMITATIONS. VERIFY THE DRINK STATION COUNTER DOORS IN THE EXIT CORRIDOR MEET THOSE LIMITATIONS. 4. SHEET A-1.1; FLOOR PLAN: INDICATE ON THE PLAN HOW THE IBC SECTION 1109.11 ACCESSIBILITY REQUIREMENTS ARE MET. 5. SHEET A-1.2; ROOF PLAN: VERIFY THE EXISTING ROOF STRUCTURE IS CAPABLE OF SUPPORTING THE NEW RTU'S AND THE NEW BUILT UP ROOF. INDICATE THIS WITH A NOTE ON THE DRAWING. 6. SHEET A-4; ELEVATIONS J AND K: LOCATE THE PAPER DISPENSER PER THE ICC/ANSI A117.1-2003, FIGURE 604.7. 7. SHEET A-4.2; NORTH, EAST AND SOUTH ELEVATIONS: NOTE 4 INDICATES TO COORDINATE CUTTING OF THE EXISTING MASONRY WITH STRUCTURAL. PROVIDE STRUCTURAL ANALYSIS AND DETAILS FOR THE NEW OPENINGS. 8. SHEET A6.1; FINISH SCHEDULE: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 9. SHEET A-9; DETAIL 9: SHOW AN ENLARGED PLAN OF THE HOT WATER HEATER SUPPORT WALLS/JOISTS. INDICATE ALL CONNECTIONS. 10. SHEET A-11; SECTION 1: INDICATE HOW THE STEEL COLUMN IS SUPPORTED. PROVIDE STRUCTURAL DETAIL INDICATING ALL STRUCTURAL MEMBER AND CONNECTION. 11. SHEET A-13; NOTE 5: THIS NOTE WILL BE INCLUDED IN THE LOCKS, HOLDS AND NOTICES COMMENTS. 12. SHEET A-13; SECTION B: INCLUDE VERBIAGE ON HOW THE NEW 12" BOND BEAM (NOTE 3) IS TO BE CONSTRUCTED IN EXISTING WALLS. 13. GENERAL: PROVIDE DETAILS FOR ANY NEW OPENINGS IN EXISTING WALLS. 14. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 11/02/2011 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 106.3.1, IPC 2006. |
| 11/02/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The controlling code for gas piping is the 2006 International Fuel Gas Code, not the 2000 Uniform Mechanical Code. 2. Show the location and size of the water heater vent. Show that it complies with the termination requirements of Section 503.8 (3), IFGC 2006. 3. Verify the natural gas input for the rooftop units; coordinate with the mechanical specifications. 4. Provide the natural gas pipe sizing calculations. Verify the size of the natural gas branch pipe serving the water heater. Reference: Section 402.3, IFGC 2006. 5. Provide site drawing showing the size, route, termination, and slope of the building sewer. Reference: Section 106.3.1, IPC 2006. 6. Show the location of the grease interceptor, show which fixtures are connected to it, and provide an installation detail. Reference: Section 106.3.1, IPC 2006. 7. Provide water pressure and water pipe sizing calculations. Reference: Section 604.1, IPC 2006. 8. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Section 802.1, IPC 2006. 9. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). Reference: Section 402.1, UPC 2006, as amended by the City of Tucson. 10. Appliances (e.g. soda dispensers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2006. 11. Provide cleanouts for all horizontal drains, sized for the drains they serve. Reference: Sections 708.3.1 and 708.7, IPC 2006. 12. Revise the sanitary waste isometric to show the individual vents connected to the fixture drains, not to the horizontal drains. Reference: Section 907.1, IPC 2006. 13. Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1107, IPC 2006. |
| 11/02/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/02/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 11/02/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 3. Show the size, routing, and termination of the condensate drains for the rooftop units. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006. 4. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. exhaust shall run whenever supply air is introduced into the restrooms). Reference: Section 403.2.1 (4), IMC 2006. 5. Show that the proposed water-cooled ice maker complies with the water conservation requirements of Section 1201.3, IMC 2006, as amended by the City of Tucson. |
| 11/03/2011 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 11/03/2011 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/03/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Sheet A1 Walls P1 and P1A need to be one hour rated between backroom and rest rooms. The corridor doors from the restrooms need to be 20 minute rated. See IFC Section 1017. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/03/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |