Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

SECTIONS - DETAILS:

1. Show wood framing members resting on concrete as pressure treated, R319.1 item 2.
2. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.

MECHANICAL PLANS:

1. Provide return air duct and register sizes meeting minimum requirements of 72 SQ IN/ ton, M1403. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN per 1,000 BTU (1 ton cooling = 12,000 BTU). Change the 15" return air duct to a minimum of 22".

ELECTRICAL PLANS:

1. Peninsular counter tops require at least one receptacle outlet within 12" below the countertop surface, E3801.4.2 and E3801.4.3. Add a receptacle at the peninsula end.
2. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3603.2 and E3801.3 through E3801.4.5.
3. Provide an exterior outlet at grade level located at both the front and back of the dwelling, E3801.7. These outlets require GFCI protected E3802.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Show the installation of minimum required "R" values of insulation where gypsum board is installed at ceilings and exterior walls, N1101.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review