Permit Number: T11CM03363
Parcel: 10610005D

Address:
2020 W PRINCE RD

Review Status: Completed

Review Details: SITE

Permit Number - T11CM03363
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2011 RBROWN1 ADA REVIEW Passed
11/07/2011 DAVE MANN FIRE REVIEW Approved
11/07/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the public sanitary sewer
b. the location of the building connections to the public sewer
c. the location, invert, and rim elevation of the upstream and downstream manholes and cleanouts
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006 and Section 710.1, UPC 2006, as amended by the City of Tucson.
11/07/2011 RONALD BROWN H/C SITE REVIEW Denied RESUBMITTAL NON RESPONSIVE TO FRIST SUBMITTAL DENIAL
1. Provide large scale detail of West end of new marked crossing: ramp, detectable warning strip etc.
2. Provide detetctable warning strip, north curb and 5' turn aroung at East landing of marked crossing.
3. Indicate slopes of marked crossing as per ANSI 117.1, section 403.3.
END OF REVIEW
11/08/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: American Home Furnishings - Site
T11CM03363
Site Plan (1st Review)

TRANSMITTAL DATE: November 10, 2011

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for full code compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for the areas of change to the site only, no building expansion proposed.

2. Once negotiations are complete for the right-of-way the parcels will need to be combined. Provide a Pima County Tax Parcel Combo and a recorded covenant regarding development and use of real property.

3. Add a note to the plan stating "THIS SITE PLAN IS DESIGNED TO MEET THE REQUIREMENTS OF THE OVERLAY ZONES, MAJOR STREETS AND ROUTES (MS&R) SETBACK ZONE".

4. D.S. 2-02.2.1.A.5 Provide the height for all existing buildings within the footprint on the site plan..

5. D.S. 2-02.2.1.A.9 Show the existing bicycle parking on the site plan.

6. D.S. 2-02.2.1.A.10 Provide sight visibility triangles (SVT) for the PAALs access from Prince.

7. D.S. 2-02.2.1.A.12 Sheet A2.0 provide a width dimension for the PAAL access from Prince.

8. D.S. 2-02.2.1.A.12 Sheet A3.0 provide a width dimension for the west PAAL that provides access to the proposed new parking area

9. D.S. 2-02.2.1.A.12 There appears to be a fence proposed along the southern property line. That said per LUC Section 3.3.6.6.B.2 Access lanes and PAALs shall be setback at least two (2) feet from a wall, screen, or other obstruction. Show the required two (2) foot setback on the site plan.

10. D.S. 2-02.2.1.A.18 Label Price Road as an MS&R route.

11. D.S. 2-02.2.1.A.20 Provide a copy of the cross access and parking agreement. Provide the recordation information, sequence number, on the site plan as a note.

12. D.S. 2-02.2.1.A.25 If applicable provide existing and proposed lighting layout and type.

13. D.S. 2-02.2.2.A.3 Provide a Floor Area Ration (FAR) per LUC 3.2.11.2.C

14. D.S. 2-02.2.2.A.4 As the new vehicle parking calculation have been used on this project provide a bicycle parking calculation the meets the requirements of LUC Section 3.3.8.2.B.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\site\t11cm03363.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan
11/17/2011 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 11/30/2011

Drainage Statement:

The drainage statement is acceptable and hereby approved for the proposed improvements.

Site Plan:

Provide the following information on the site plan:

1. Revise the owner's name in the Title Block (i.e. Tananger Property)
2. Label and dimension the curb openings between the raised parking islands in front of the eastern building (D.S. 2-02.2.1.A.06).
3. Provide existing and future sight visibility triangles (D.S. 2-02.2.1.A.10).
4. Provide the proposed driveway widths (D.S. 2-02.2.1.A.11).
5. Show the regulatory floodplain limits and water surface elevations (D.S. 2-02.2.1.A.15).
6. Provide drainage arrows to clarify drainage patterns (D.S. 2-02.2.1.A.16).
7. It appears from the proposed grades in front of the eastern building, water will potentially enter the building. Address this issue and verify that the water will not enter the building (D.S. 2-02.2.1.A.16).
8. Provide the cut and fill quantities (D.S. 2-02.2.1.A.17).
9. The location of the refuse container is not clear. Show the proposed location and ensure it is accessible, especially with the proposed entrance changes (D.S. 2-02.2.1.A.32)
11/30/2011 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Note: Existing development on the site is subject to the zoning regulations in effect at the time the existing development received zoning approval per LUC 3.7.1.2.B

2. Ensure that all Zoning & Engineering comments and concerns are addressed

3. Additional comments may apply
12/02/2011 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2012 CPIERCE1 OUT TO CUSTOMER Completed
04/06/2012 SUE REEVES REJECT SHELF Completed