Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03265
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2011 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 10/13/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the size, route, and termination of the condensate drain for the new A/C unit. |
| 10/13/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/13/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/13/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 2. SHEET A2; NOTE AT ENTRY: A PLAN NOTE INDICATES 'STRUCTURAL COLUMNS C1 TO BE LOCATED ON SITE AS COORDINATED BY THE G.C. PER S-1.0'. THERE ARE NO C1 COLUMNS LOCATED ON SHEET S1. PROVIDE. 3. SHEET A5; RESTROOM ELEVATIONS 5 AND 7: PROVIDE DIMENSIONS FOR GRAB BAR LENGTHS AND LOCATIONS, AND LOCATION OF THE PAPER DISPENSER, PER THE ICC/ANSI A117.1-2003, FIGURE 604.5.1. |
| 10/13/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 10/13/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/13/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/14/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/13/2011 | FRODRIG2 | ADA | REVIEW | Needs Review | |
| 12/13/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |