Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM03234
Parcel: 11202033H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03234
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/01/2011 ROBERT SHERRY WATER REVIEW Approved
11/01/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Specify the exhaust fans noted on sheet 4 with respect to the air flow rate. Show the size of the exhaust duct work required and the termination of the exhaust duct.
11/01/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the listing information for the Hydro Sun unit. Reference: Section 301.1, UPC 2006.
2. Clarify how the Hydro Sun unit is to be connected to the snitary drain system. Show why it should be directly connected instead of indirectly wasted. Reference Section 807.1, UPC 2006.
3. Provide water pressure calculations. Note that the minimum required water pressure for the Hydro Sun unit is 50 PSI.
4. Provide backflow protection for the water connections to the Hydro Sun unit if it is not provided with the unit.
11/14/2011 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2011 DELMA ROBEY OUT TO CUSTOMER Completed