Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03234
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/01/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/01/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/01/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Specify the exhaust fans noted on sheet 4 with respect to the air flow rate. Show the size of the exhaust duct work required and the termination of the exhaust duct. |
11/01/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the listing information for the Hydro Sun unit. Reference: Section 301.1, UPC 2006. 2. Clarify how the Hydro Sun unit is to be connected to the snitary drain system. Show why it should be directly connected instead of indirectly wasted. Reference Section 807.1, UPC 2006. 3. Provide water pressure calculations. Note that the minimum required water pressure for the Hydro Sun unit is 50 PSI. 4. Provide backflow protection for the water connections to the Hydro Sun unit if it is not provided with the unit. |
11/14/2011 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/14/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |