Permit Number: T11CM03234
Parcel: 11202033H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03234
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT: PROVIDE THE CODE ANALYSIS INFORMATION ON THE DRAWINGS. THE ACCESSIBILITY CODE IS THE ICC/ANSI A117.1-2003.
2. SHEET 3: REMOVE THE NOTE "HANDICAPPED ACCESSIBLE" ON THE RESTROOM ON THE SOUTH WALL.
3. SHEET 6: ARRANGE THE WATER CLOSET/SINK TO MEET ICC/ANSI A117.1-2003, FIGURE 604.3 SPACE REQUIREMENTS.
4. SHEET 6: ADD A VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.1.
5. SHEET 6: LOCATE THE PAPER DISPENSER PER ICC/ANSI A117.1-2003, FIGURE 604.7.
6. SHEET 3: INDICATE THE EXISTING SERVICE SINK IN THE JANITOR ROOM.
7. SHEET 3: INDICATE THE STRUCTURAL INTERIOR WALL AND THE EXISTING DRINKING FOUNTAIN.
11/01/2011 FRODRIG2 WATER REVIEW Needs Review
11/01/2011 FRODRIG2 MECHANICAL-COMMERCIAL REVIEW Needs Review
11/01/2011 FRODRIG2 PLUMBING-COMMERCIAL REVIEW Needs Review
11/01/2011 FRODRIG2 WWM REVIEW Needs Review