Permit Number: T11CM03234
Parcel: 11202033H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03234
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
10/11/2011 LOREN MAKUS ENGINEERING REVIEW Approved
10/12/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/12/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE A CODE ANALYSIS ON THE DRAWINGS, INCLUDING SQUARE FOOTAGE, OCCUPANCY TYPE, OCCUPANCY LOAD, CONSTRUCTION TYPE, ETC.
2. SHEET 3: THE SHOWER MUST BE ACCESSIBLE. PROVIDE AN ENLARGED PLAN AND DETAILS ON THE DRAWINGS PER THE ICC/ANSI A117.1-2003, SECTION 608.
3. SHEET 3: PROVIDE ENLARGED PLANS OF THE RESTROOMS ON THE DRAWINGS PER THE ICC/ANSI A117.1-2003, SECTION 604. INCLUDE ELEVATIONS INDICATING GRAB BARS, PAPER DISPENSER, ETC.
10/12/2011 ERIC NEWCOMB ADA REVIEW Passed
10/12/2011 DAVE MANN FIRE REVIEW Approved
10/12/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/26/2011 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
10/26/2011 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
10/26/2011 CPIERCE1 WATER REVIEW Needs Review
10/26/2011 CPIERCE1 WWM REVIEW Needs Review