Permit Number: T11CM03218
Parcel: 107031890

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03218
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2011 MICHAEL ST. PAUL ZONING REVIEW Denied Site plan and review required.
10/11/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the installed weight of the ERV and show how it is to be connected to the building structure.
2. Show how FC-1 is to be connected to the building structure.
10/11/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/11/2011 ROBERT SHERRY WATER REVIEW Approved
10/11/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide suspended fan coil unit structural calculations.
2. Please provide accessible drinking fountains.
3. Demising wall between offices and kennel area should be detail 7/A2.1.
4. All other new partitions in office area to be type W1a.
END OF REVIEW
10/11/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/11/2011 DAVE MANN FIRE REVIEW Approved
10/11/2011 RONALD BROWN ADA REVIEW Passed
10/11/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/24/2011 GBONILL1 WWM REVIEW Needs Review
10/24/2011 GBONILL1 ENGINEERING REVIEW Needs Review