Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03218
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/11/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | Site plan and review required. |
| 10/11/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the installed weight of the ERV and show how it is to be connected to the building structure. 2. Show how FC-1 is to be connected to the building structure. |
| 10/11/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/11/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/11/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide suspended fan coil unit structural calculations. 2. Please provide accessible drinking fountains. 3. Demising wall between offices and kennel area should be detail 7/A2.1. 4. All other new partitions in office area to be type W1a. END OF REVIEW |
| 10/11/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/11/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/11/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 10/11/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/24/2011 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 10/24/2011 | GBONILL1 | ENGINEERING | REVIEW | Needs Review |