Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2011 DAVE MANN FIRE REVIEW Approv-Cond 1. Need seperate permits for tanks.
2. Bollards need to meet IFC section 312. Needs to be 4 feet in every direction.
11/16/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 2: THE NOTE 2 ON SHEET CA-2 INDICATES THE 2006 IBC SECTION 1805.7.2.2 WAS USED IN THE FOUNDATION DESIGN, AND DESIGN CRITERIA PER THE SOILS REPORT WAS USED. REMOVE THE REFERENCE TO THE IBC SINCE A REPORT IS PROVIDED.
2. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/17/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/17/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/17/2011 ROBERT SHERRY WATER REVIEW Approved
11/21/2011 SREEVES1 WWM REVIEW Passed
12/01/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/02/2011 PAUL MACHADO ENGINEERING REVIEW Approved
12/05/2011 TERRY STEVENS ZONING REVIEW Denied 11/05/2011

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.