Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM03202
Parcel: 10511061R

Address:
220 W WETMORE RD

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T11CM03202
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2012 CPIERCE1 OUT TO CUSTOMER Completed