Permit Number: T11CM03197
Parcel: 12703001A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03197
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified backflow preventer assembly, BP1 (Watts model 007), is a double check valve assembly, not a reduced pressure zone backflow assembly. [Second comment: The specified backflow preventer assembly, BP1, is a double check valve assembly, not a reduced pressure zone backflow assembly. It is suitable for your intended use but unlike the reduced pressure zone backflow assembly, it does not have a drain. If the backflow assemblies (BP1 and BP2) are located in a location remote from the appliance to which they are connected, provide a permanent label for each valve assembly per Section 603.3.2, UPC 2006. Each backflow assembly shall be installed with access and clearances per Section 603.3.4, UPC 2006.] [Original comment: Specify the type of backflow prevention device required for the water connection to each appliance (note #1, sheet P1.2). Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.]
2. Reprint sheet P1.1; key notes 1 and 6 are only partially printed and keynotes 2-5 are missing.
01/05/2012 GERRY KOZIOL WWM REVIEW Denied 1. CIRCLE K - D11-0006
2. NEED TO IDENTIFY ALL WASTEWATER PLUMBING FIXTURES REMOVED FOR CREDIT - NEED WASTEWATER 5TH FLOOR CRDIT EVALUATION - 740-6602 OR 740-6606
3. NEED PCRWRD 3RD FLOOR CAPACITY REVIEW - KURT STEMM 740-6607 WW/IWC REVIEW OF GREASE INTERCEPTOR - TOM TOMCHAK 5025 W INA RD - 443-6200
5. NEED WASTEWATER REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - CHAD AMATEAU - 740-6547
12/22/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/27/2011 TERRY STEVENS ZONING REVIEW Approved