Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03197
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified backflow preventer assembly, BP1 (Watts model 007), is a double check valve assembly, not a reduced pressure zone backflow assembly. [Second comment: The specified backflow preventer assembly, BP1, is a double check valve assembly, not a reduced pressure zone backflow assembly. It is suitable for your intended use but unlike the reduced pressure zone backflow assembly, it does not have a drain. If the backflow assemblies (BP1 and BP2) are located in a location remote from the appliance to which they are connected, provide a permanent label for each valve assembly per Section 603.3.2, UPC 2006. Each backflow assembly shall be installed with access and clearances per Section 603.3.4, UPC 2006.] [Original comment: Specify the type of backflow prevention device required for the water connection to each appliance (note #1, sheet P1.2). Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.] 2. Reprint sheet P1.1; key notes 1 and 6 are only partially printed and keynotes 2-5 are missing. |
| 01/05/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. CIRCLE K - D11-0006 2. NEED TO IDENTIFY ALL WASTEWATER PLUMBING FIXTURES REMOVED FOR CREDIT - NEED WASTEWATER 5TH FLOOR CRDIT EVALUATION - 740-6602 OR 740-6606 3. NEED PCRWRD 3RD FLOOR CAPACITY REVIEW - KURT STEMM 740-6607 WW/IWC REVIEW OF GREASE INTERCEPTOR - TOM TOMCHAK 5025 W INA RD - 443-6200 5. NEED WASTEWATER REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - CHAD AMATEAU - 740-6547 |
| 12/22/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/27/2011 | TERRY STEVENS | ZONING | REVIEW | Approved |